815 Kimberly Drive, Carol Stream, Illinois 60188

Phone: (800) 624-8642  Fax: (866) 466-9335

E-Mail: info@wardind.com

 
 
 

Home

Company

Products

Literature

News

Contact Us

Links

Search

 

 

 

   

FIRE DAMPERS


Model 75

UL Listed 1.5 Hour Fire Damper

Type VA and HA  

  • Rollformed 22 gauge galvanized frame

  • Rollformed 22 gauge galvanized blades

  • Stainless steel closure spring (horizontal models only)

  • Available in vertical (V) or horizontal (H) models

  • Available in both single and multi-section units

  • Maximum single unit size (damper):    

  •       Vertical: 60”x60”

  •       Horizontal: 60”x60”

  • Maximum multiple unit size (damper):

  •       Vertical: 120”x120”

  •       Horizontal: 102”x60”

  • Available in stainless steel

  • UL Listed curtain-style fire damper for static systems

  • Tested to UL 555: File R16475

  • Meets NFPA 90A requirements

  • Listed with California State Fire Marshall: Listing 3225-1577:100

  • Reference 75/105 Series sizing chart for damper sizing

  • Reference 75 Series Installation Instructions

Submittal Drawing

Type VB and HB

Submittal Drawing

Type VC and HC

Submittal Drawing

Sizing Chart

Installation Instructions for Masonry Construction

Installation Instructions for Wood and Gypsum Construction

Installation Instructions for Sleeves
Installation Instructions for Breakaway Connections


Model 85

UL Listed 1.5 Hour Fire Damper

Type VA and HA  

  • Rollformed 22 gauge galvanized frame

  • Rollformed 22 gauge galvanized blades

  • Stainless steel closure spring (horizontal models only)

  • Available in vertical (V) or horizontal (H) models

  • Available as single units only

  • Maximum single unit size (damper):    

  •       Vertical: 41”x36” or 36”x60”

  •       Horizontal: 60”x60”

  • Thinline frame for applications with space constraints

  • UL Listed curtain-style fire damper for static systems

  • Tested to UL 555: File R16475

  • Meets NFPA 90A requirements

  • Listed with California State Fire Marshall: Listing 3225-1577:100

  • Reference 85/95 Series sizing chart for damper sizing

  • Reference 85 Series Installation Instructions

Submittal Drawing

Type VB and HB

Submittal Drawing

Type VC and HC

Submittal Drawing

Sizing Chart

Installation Instructions for Masonry Construction

Installation Instructions for Wood and Gypsum Construction

Installation Instructions for Sleeves
Installation Instructions for Breakaway Connections


Model 95

UL Listed 3.0 Hour Fire Damper

Type VA  

  • Rollformed 22 gauge galvanized frame

  • Rollformed 22 gauge galvanized blades

  • Available in vertical (V) models only

  • Available as single units only

  • Maximum single unit size (damper):    

  •       Vertical: 48”x49”

  • Thinline frame for applications with space constraints

  • UL Listed curtain-style fire damper for static systems

  • Tested to UL 555: File R16481

  • Meets NFPA 90A requirements

  • Listed with California State Fire Marshall: Listing 3225-1577:102

  • Reference 85/95 Series sizing chart for damper sizing

  • Reference 95 Series Installation Instructions

Submittal Drawing

Type VB

Submittal Drawing

Type VC

Submittal Drawing

 

Sizing Chart
Installation Instructions for Masonry Construction
Installation Instructions for Sleeves
Installation Instructions for Breakaway Connections


Model 105

UL Listed 3.0 Hour Fire Damper

Type VA  

  • Rollformed 22 gauge galvanized frame

  • Rollformed 22 gauge galvanized blades

  • Available in vertical (V) models only

  • Available as single units only

  • Maximum single unit size (damper):

  •       Vertical: 60”x48”

  • UL Listed curtain-style fire damper for static systems

  • Tested to UL 555: File R16481

  • Meets NFPA 90A requirements

  • Listed with California State Fire Marshall: Listing 3225-1577:102

  • Reference 75/105 Series sizing chart for damper sizing

  • Reference 105 Series Installation Instructions

Submittal Drawing

 

Type VB

Submittal Drawing

 

Type VC

Submittal Drawing

Sizing Chart

Installation Instruction for Masonry Construction

Installation Instructions for Sleeves

Installation Instructions for Breakaway Connections


Model FDS S

Fire Damper Sleeve Assembly

Type A  

  • UL Listed fire damper factory mounted in a galvanized sleeve

  • Available in the following lengths:

  •       8”

  •       12”

  •       16”

  •       20”

  • Available in the following gauges:

  •       14

  •       16

  •       18

  •       20

  •       22

  • Available in stainless steel (with model 75 only)

  • Damper can be ordered off-set from center for sidewall applications

  • Provides a fastening site for ductwork leading to the damper

  • Provides a platform to which retaining angle can be mounted

  • Reference Sleeve Installation Instructions

Submittal Drawing

Type B

Submittal Drawing

Type C

Submittal Drawing

Installation Instructions for Sleeves

Installation Instructions for Breakaway Connections

   
   

© 2009 Commercial Products Group of Hart & Cooley, Inc.